Skip to main content
  • SLIO

013-CCF0R00 - CPUs | CPUs STEP7 programmierbar, C-Klasse

Order no.

013-CCF0R00

TypeVIPA CPU 013C
Module ID-

General information

Note-
Featurespowered by SPEED7
work memory [KB]: 64 - 128
onboard 16 DI / 12 DO / 2 AI [voltage 0...10 V] ] / 4 Counter / 2 [PWM/Pulse Train]
interface [2x RJ45]: active Ethernet PG/OP communication with DHCP support, switch, ModbusTCP master/slave, openCommunication, SmartPROFINET (iDevice and Control up to 8 Device)
interface [RS485]: MPI, PtP: ASCII, STX/ETX, 3964 (R), USS master, Modbus master/slave
optional: PROFIBUS master/slave
web server
SD card slot with locking, up to 64 expansion modules, configurable with SPEED7 Studio, SIMATIC Manager and TIA Portal

Technical data power supply

Power supply (rated value)DC 24 V
Power supply (permitted range)DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation)120 mA
Current consumption (rated value)360 mA
Inrush current3 A
I²t0.1 A²s
Max. current drain at backplane bus1 A
Max. current drain load supply6 A
Power loss7 W
Number of outputs1
Output voltage (typ)L+ (-1.5 V)
Output voltage (rated value)300 mA
Short-circuit protectionyes, electronic
Binding of potentialPower supply of PLC

Communication functions

PG/OP channel
Global data communication
Number of GD circuits, max.8
Size of GD packets, max.54 Byte
S7 basic communication
S7 basic communication, user data per job76 Byte
S7 communication
S7 communication as server
S7 communication as client-
S7 communication, user data per job160 Byte
Number of connections, max.32

PWM data

PWM channels2
PWM time basis1 µs / 0.1 ms / 1 ms
Period length50µs...65.535ms / 0.1...87ms / 1...87ms
Minimum pulse width0...0.5 * Period duration
Type of outputHighside

Functionality Sub-D interfaces

TypeX3
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated
MPI
MP²I (MPI/RS232)-
DP masteroptional
DP slaveoptional
Point-to-point interface
5V DC Power supplymax. 90mA, isolated
24V DC Power supplymax. 100mA, non-isolated

Type-
Type of interface-
Connector-
Electrically isolated-
MPI-
MP²I (MPI/RS232)-
DP master-
DP slave-
Point-to-point interface-
5V DC Power supply-
24V DC Power supply-

Functionality MPI

Number of connections, max.32
PG/OP channel
Routing
Global data communication
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Transmission speed, min.19.2 kbit/s
Transmission speed, max.12 Mbit/s

Functionality PROFIBUS master

PG/OP channel
Routing
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Activation/deactivation of DP slaves-
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Number of DP slaves, max.32
Address range inputs, max.2 KB
Address range outputs, max.2 KB
User data inputs per slave, max.244 Byte
User data outputs per slave, max.244 Byte

Functionality PROFIBUS slave

PG/OP channel
Routing
S7 communication
S7 communication as server
S7 communication as client-
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Automatic detection of transmission speed
Transfer memory inputs, max.244 Byte
Transfer memory outputs, max.244 Byte
Address areas, max.32
User data per address area, max.32 Byte

Point-to-point communication

PtP communication
Interface isolated
RS232 interface-
RS422 interface-
RS485 interface
ConnectorSub-D, 9-pin, female
Transmission speed, min.150 bit/s
Transmission speed, max.115.5 kbit/s
Cable length, max.500 m

Point-to-point protocol

ASCII protocol
STX/ETX protocol
3964(R) protocol
RK512 protocol-
USS master protocol
Modbus master protocol
Modbus slave protocol
Special protocols-

Functionality RJ45 interfaces

TypeX1/X2
Type of interfaceEthernet 10/100 MBit Switch
Connector2 x RJ45
Electrically isolated
PG/OP channel
Number of connections, max.4
Productive connections
Fieldbus-

Type-
Type of interface-
Connector-
Electrically isolated-
PG/OP channel-
Number of connections, max.-
Productive connections-
Fieldbus-

Ethernet communication via PG/OP

Number of productive connections via PG/OP, max.2
Number of productive connections by Siemens NetPro, max.2
S7 connectionsBSEND, BRCV, GET, PUT, Connection of active and passive data handling
User data per S7 connection, max.64 KB
TCP-connectionsFETCH PASSIV, WRITE PASSIV, Connection of passive data handling
User data per TCP connection, max.8 KB
ISO on TCP connections (RFC 1006)FETCH PASSIV, WRITE PASSIV, Connection of passive data handling
User data per ISO connection, max.8 KB

Ethernet open communication via PG/OP

Number of configurable connections, max.2
ISO on TCP connections (RFC 1006)TSEND, TRCV, TCON, TDISCON
User data per ISO on TCP connection, max.32 KB
TCP-Connections nativeTSEND, TRCV, TCON, TDISCON
User data per native TCP connection, max.32 KB
User data per ad hoc TCP connection, max.1460 Byte
UDP-connectionsTUSEND, TURCV
User data per UDP connection, max.1472 Byte

Housing

MaterialPPE / PPE GF10
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)147 mm x 100 mm x 83 mm
Net weight320 g
Weight including accessories320 g
Gross weight355 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationin preparation
KC certificationin preparation