Skip to main content
  • SLIO

015-CEFPR01 - CPUs | CPUs STEP7 programmable, PROFINET

Order no.

015-CEFPR01

TypeVIPA CPU 015PN
Module ID-

General information

Note-
Featurespowered by SPEED7
work memory [KB]: 256 - 512
integrated PROFINET controller
interface [2x RJ45]: PROFINET, ModbusTCP master/slave, openCommunication, SmartPROFINET (iDevice and Control up to 8 Device)
interface [2x RJ45]: active Ethernet PG/OP communication with DHCP support, switch
interface [2x RS485]: MPI, PtP: ASCII, STX/ETX, 3964(R), USS master, Modbus master/slave
optional: PROFIBUS master/slave
web server
SD card slot with locking, up to 64 expansion modules, configurable with SPEED7 Studio, SIMATIC Manager and TIA Portal

Technical data power supply

Power supply (rated value)DC 24 V
Power supply (permitted range)DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation)150 mA
Current consumption (rated value)1.1 A
Inrush current3 A
I²t0.1 A²s
Max. current drain at backplane bus3 A
Max. current drain load supply10 A
Power loss7.5 W

Communication functions

PG/OP channel
Global data communication
Number of GD circuits, max.8
Size of GD packets, max.22 Byte
S7 basic communication
S7 basic communication, user data per job76 Byte
S7 communication
S7 communication as server
S7 communication as client-
S7 communication, user data per job160 Byte
Number of connections, max.32

Functionality Sub-D interfaces

TypeX2
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated
MPI
MP²I (MPI/RS232)-
DP master-
DP slave-
Point-to-point interface
5V DC Power supplymax. 90mA, isolated
24V DC Power supplymax. 100mA, non-isolated

TypeX3
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated
MPI
MP²I (MPI/RS232)-
DP masteroptional
DP slaveoptional
Point-to-point interface-
5V DC Power supplymax. 90mA, isolated
24V DC Power supplymax. 100mA, non-isolated

Functionality MPI

Number of connections, max.32
PG/OP channel
Routing
Global data communication
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Transmission speed, min.19.2 kbit/s
Transmission speed, max.12 Mbit/s

Functionality PROFIBUS master

PG/OP channel
Routing
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Activation/deactivation of DP slaves-
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Number of DP slaves, max.124
Address range inputs, max.2 KB
Address range outputs, max.2 KB
User data inputs per slave, max.244 Byte
User data outputs per slave, max.244 Byte

Functionality PROFIBUS slave

PG/OP channel
Routing
S7 communication
S7 communication as server
S7 communication as client-
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Automatic detection of transmission speed-
Transfer memory inputs, max.244 Byte
Transfer memory outputs, max.244 Byte
Address areas, max.32
User data per address area, max.32 Byte

Point-to-point communication

PtP communication
Interface isolated
RS232 interface-
RS422 interface-
RS485 interface
ConnectorSub-D, 9-pin, female
Transmission speed, min.150 bit/s
Transmission speed, max.115.5 kbit/s
Cable length, max.500 m

Point-to-point protocol

ASCII protocol
STX/ETX protocol
3964(R) protocol
RK512 protocol-
USS master protocol
Modbus master protocol
Modbus slave protocol
Special protocols-

Functionality PROFINET I/O controller

Realtime Class-
Conformance ClassPROFINET IO
Number of  PN IO devices128
IRT support-
Prioritized start-up-
Number of PN IO lines1
Address range inputs, max.2 KB
Address range outputs, max.2 KB
Transmiting clock1 ms
Update time1 ms .. 512 ms
Isochronous mode-

Functionality RJ45 interfaces

Type-
Type of interfaceEthernet 10/100 MBit Switch
Connector2 x RJ45
Electrically isolated
PG/OP channel
Number of connections, max.4
Productive connections
Fieldbus-

Type-
Type of interfaceEthernet 10/100 MBit Switch
Connector2 x RJ45
Electrically isolated
PG/OP channel
Number of connections, max.8
Productive connections
FieldbusPROFINET-IO

Ethernet communication CP

Number of configurable connections, max.8
Number of productive connections by Siemens NetPro, max.8
S7 connectionsBSEND, BRCV, GET, PUT, Connection of active and passive data handling
User data per S7 connection, max.32 KB
TCP-connectionsFETCH PASSIV, WRITE PASSIV, Connection of passive data handling
User data per TCP connection, max.8 KB
ISO-connections-
User data per ISO connection, max.-
ISO on TCP connections (RFC 1006)FETCH PASSIV, WRITE PASSIV, Connection of passive data handling
User data per ISO on TCP connection, max.8 KB
UDP-connections-
User data per UDP connection, max.-
UDP-multicast-connections-
UDP-broadcast-connections-

Ethernet open communication

Number of connections, max.8
ISO on TCP connections (RFC 1006)TSEND, TRCV, TCON, TDISCON
User data per ISO on TCP connection, max.32 KB
TCP-Connections nativeTSEND, TRCV, TCON, TDISCON
User data per native TCP connection, max.32 KB
User data per ad hoc TCP connection, max.1460 Byte
UDP-connectionsTUSEND, TURCV
User data per UDP connection, max.1472 Byte

Ethernet communication via PG/OP

Number of productive connections via PG/OP, max.4
Number of productive connections by Siemens NetPro, max.4
S7 connectionsBSEND, BRCV, GET, PUT, Connection of active and passive data handling
User data per S7 connection, max.64 KB
TCP-connectionsFETCH PASSIV, WRITE PASSIV, Connection of passive data handling
User data per TCP connection, max.8 KB
ISO on TCP connections (RFC 1006)FETCH PASSIV, WRITE PASSIV, Connection of passive data handling
User data per ISO connection, max.8 KB

Ethernet open communication via PG/OP

Number of configurable connections, max.4
ISO on TCP connections (RFC 1006)TSEND, TRCV, TCON, TDISCON
User data per ISO on TCP connection, max.32 KB
TCP-Connections nativeTSEND, TRCV, TCON, TDISCON
User data per native TCP connection, max.32 KB
User data per ad hoc TCP connection, max.1460 Byte
UDP-connectionsTUSEND, TURCV
User data per UDP connection, max.1472 Byte

Management & diagnosis

ProtocolsICMP
DCP
DHCP via PG/OP
NTP via CP
Web based diagnosis
NCM diagnosis

Housing

MaterialPPE / PPE GF10
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)131.5 mm x 109 mm x 83 mm
Net weight330 g
Weight including accessories330 g
Gross weight365 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationin preparation
KC certificationyes