032-1BB30 - Signal modules analog | Analog output modules
Order no. |
032-1BB30 |
Type | SM 032 |
Module ID | 0501 25D8 |
General information | |
Note | - |
Features | 2x AO 12 Bit Voltage 0…10 V |
Current consumption/power loss |
|
Current consumption from backplane bus | 85 mA |
Current consumption from load voltage L+ (without load) | 35 mA |
Power loss | 1.2 W |
Technical data analog outputs |
|
Number of outputs | 2 |
Cable length, shielded | 200 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | ![]() |
Current consumption from rated load voltage | - |
Voltage output short-circuit protection | ![]() |
Voltage outputs | ![]() |
Min. load resistance (voltage range) | 5 kΩ |
Max. capacitive load (current range) | 1 µF |
Max. inductive load (current range) | 10 mA |
Output voltage ranges | 0 V ... +10 V |
Operational limit of voltage ranges | +/-0.3% |
Basic error limit voltage ranges | +/-0.2% |
Destruction limit against external applied voltage | max. 24V |
Current outputs | - |
Max. in load resistance (current range) | - |
Max. inductive load (current range) | - |
Typ. open circuit voltage current output | - |
Output current ranges | - |
Operational limit of current ranges | - |
Basic error limit current ranges | - |
Destruction limit against external applied voltage | - |
Settling time for ohmic load | 1.5 ms |
Settling time for capacitive load | 2 ms |
Settling time for inductive load | - |
Resolution in bit | 12 |
Conversion time | 2 ms all channels |
Substitute value can be applied | no |
Output data size | 4 Byte |
Status information, alarms, diagnostics |
|
Status display | yes |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | yes |
Diagnostics information read-out | possible |
Supply voltage display | green LED |
Group error display | red LED |
Channel error display | red LED per channel |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | ![]() |
Between channels and power supply | ![]() |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | - |
Max. potential difference between Mana and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | - |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Datasizes |
|
Input bytes | 0 |
Output bytes | 4 |
Parameter bytes | 8 |
Diagnostic bytes | 20 |
Housing | |
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Net weight | 60 g |
Weight including accessories | 60 g |
Gross weight | 74 g |
Environmental conditions | |
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | yes |